National unified service hotline : 0086-400-8010-113

Current Location : Home > Products > Tianweixing Series - Low Temperature Air Energy Heat Pump (Chilled Water) Unit

Tianweixing Series - Low Temperature Air Energy Heat Pump (Chilled Water) Unit

Tianweixing series low-temperature air energy heat pump (chilled water) units use low-temperature vortex jet reheat compressors, R410A environmentally friendly refrigerant, high-efficiency heat exchangers and other world-renowned brand components. It can efficiently heat at -35℃ in winter and stably cool at +50℃ in summer. It is an ideal choice to replace traditional high-energy heating methods such as coal, gas, oil, electric heating, and central air conditioning.

Scope of application

Heating and central air conditioning cooling & heating in hotels, guesthouses, schools, hospitals, factories, clubs, commercial buildings and other places.


  • 图片 33.png

    Internationally renowned brand compressor

  • 图片 35.png

    Brand valve parts

  • 图片 36.png

    Multi-machine module combination

  • 图片 37.png

    Run smoothly

  • 图片 39.png

    Multiple anti-freeze

  • 图片 40.png

    Wide application temperature

  • 图片 41.png

    Extremely low noise

Technical Data Sheet

Product number

DPLT-160CHW-ZDS

DPLT-175CHW-ZDS

Applicable power supply

380V~50Hz

Unit type

Floor radiation type + fan coil type + radiator type

Heating

Working condition A7℃/W45℃

Rated heat capacity

160.0kW

175.0kW

Rated heating input power

44.69kW

49.58kW

Rated heating COP

3.58

3.53

Working condition A-12℃/W41℃

Nominal heating capacity

108.0kW

118.0kW

Nominal heating input power

42.86kW

47.20kW

Nominal heating COPh

2.52

2.5

Working condition A-20℃/W41℃

Low temperature heating capacity

93.0kW

102.0kW

Low temperature heating input power

41.70kW

46.15kW

Low temperature heating COPdh

2.23

2.21

Working condition A-12℃/W55℃

Nominal heating capacity

102.0kW

110.0kW

Nominal heating input power

50.00kW

54.73kW

Nominal heating COPh

2.04

2.01

Working condition A-20°C/W55°C

Low temperature heating capacity

86.5kW

94.0kW

Low temperature heating input power

46.26kW

50.81kW

Low temperature heating COPdh

1.87

1.85

Refrigeration

Working condition A35℃/W7℃

Rated cooling capacity

130.0kW

140.0kW

Rated cooling input power

43.92kW

47.95kW

Rated refrigeration COPc

2.96

2.92

Maximum input power

60.0kW

65.7kW

Maximum input current

101A

110A

IPLV(H)

3.05

3.01

IPLV(C)

3.86

3.85

Compressor Type

Low temperature vortex + jet enthalpy increase

Refrigerant Type

R410A environmentally friendly

Water temperature setting range

10℃~55℃

Applicable working environment

-35℃~50℃

Connection size

Male thread /DN65

Male thread /DN65

Circulating water volume

  19.00m³/h

  20.50m³/h

Unit noise

 69dB(A)

 71dB(A)

Total product weight

 1130kg

 1190kg

Net size of product

 2395×1200×2400mm

 2395×1200×2400mm

◆ This product complies with GB/T25127.1-2020 and GB 37480-2019 standards;