National unified service hotline : 0086-400-8010-113

Current Location : Home > Products > Uranus Series - Variable Frequency Low Temperature Air Energy Heat Pump (Chilled Water) Unit

Uranus Series - Variable Frequency Low Temperature Air Energy Heat Pump (Chilled Water) Unit

Uranus series variable frequency low temperature air energy heat pump (chilled water) units use variable frequency low temperature jet enthalpy increase compressors and are designed for heating and central air conditioning in commercial places such as office buildings and hotels. They are an ideal choice to replace traditional high energy consumption heating methods such as coal, gas, oil, electric heating, and central air conditioning.

Scope of application

Heating and central air conditioning cooling & heating in hotels, guesthouses, schools, hospitals, factories, clubs, commercial buildings and other places.

  • 图片 33.png

    Internationally renowned brand compressor

  • 图片 4.png

    DC frequency conversion

  • 图片 35.png

    Brand valve parts

  • 图片 36.png

    Multi-machine module combination

  • 图片 37.png

    Run smoothly

  • 图片 39.png

    Multiple anti-freeze

  • 图片 40.png

    Wide application temperature

  • 图片 41.png

    Extremely low noise

Technical Data Sheet

Product number

DPLT-90CHW-VDS

DPLT-165CHW-VDS

DPLT-180CHW-VDS

Applicable power supply

380V~50Hz

Unit type

Floor radiation type + fan coil type + radiator type

Heating

Working condition A7℃/W45℃

Rated heat capacity

90.0kW

165.0kW

180.0kW

Rated heating input power

24.59kW

44.84kW

49.72kW

Rated heating COP

3.66

3.68

3.62

Working condition A-12℃/W41℃

Nominal heating capacity

65.0kW

115.0kW

125.0kW

Nominal heating input power

25.39kW

46.00kW

49.60kW

Nominal heating COPh

2.56

2.5

2.52

Working condition A-20℃/W41℃

Low temperature heating capacity

55.0kW

102.0kW

108.0kW

Low temperature heating input power

24.12kW

45.54kW

47.79kW

Low temperature heating COPdh

2.28

2.24

2.26

Working condition A-12℃/W55℃

Nominal heating capacity

60.0kW

108.0kW

112.0kW

Nominal heating input power

29.27kW

53.73kW

56.00kW

Nominal heating COPh

2.05

2.01

2

Working condition A-20℃/W55℃

Low temperature heating capacity

51.4kW

91.5kW

95.0kW

Low temperature heating input power

27.34kW

48.41kW

51.08kW

Low temperature heating COPdh

1.88

1.89

1.86

Refrigeration

Working condition A35℃/W7℃

Rated cooling capacity

75.0kW

135.0kW

145.0kW

Rated cooling input power

24.67kW

46.08kW

50.88kW

Rated refrigeration COPc

3.04

2.93

2.85

Maximum input power

35.1kW

64.5kW

67.2kW

Maximum input current

59A

108A

113A

IPLV(H)

3.02

3

3.01

IPLV(C)

4.15

4.02

4.05

Compressor Type

DC frequency conversion + low temperature vortex + jet enthalpy increase

Refrigerant Type

R410A environmentally friendly

Water temperature setting range

10℃~55℃

Applicable working environment

-35℃~50℃

Connection size

Female thread /DN50

Male thread /DN65

Male thread /DN65

Circulating water volume

  11.30m³/h

  19.80m³/h

21.50m3/h

Unit noise

 68dB(A)

 72dB(A)

75dB(A

Total product weight

 552ko

 1185kg

1252kc

Net size of product

1230×1400×2328mm

  1410x2250x2328mm

1410x2250x2328mm

◆ This product complies with GB/T25127.1-2020 and GB 37480-2019 standards;
◆ Due to continuous product optimization and improvement, changes in product models, parameters and designs will not be notified separately. Please refer to the product nameplate for details;