National unified service hotline : 0086-400-8010-113

Current Location : Home > Products > Venus series - variable frequency low temperature air energy heat pump (chilled water) unit

Venus series - variable frequency low temperature air energy heat pump (chilled water) unit

Venus series variable frequency low temperature air energy heat pump (chilled water) units, dual system design, use variable frequency low temperature jet reheat compressor, DC variable frequency fan motor, DC variable frequency drive control technology, R410A environmentally friendly refrigerant. Patented compressor "silent cabin" design, high-efficiency heat exchanger and other world-renowned brand components configuration, to create the ultimate low noise, high quality air energy. In winter, it can heat efficiently in a low temperature environment of -35℃, and in summer, it can cool stably in a high temperature environment of +50 degrees. It is an ideal choice to replace traditional high energy consumption heating methods such as coal, gas, oil, electric heating, central air conditioning, etc.

Scope of application

Heating and central air-conditioning systems for villas, mansions, shops, clubs, hotels and other places.

  • 图片 33.png

    Internationally renowned brand compressor

  • 图片 4.png

    DC frequency conversion

  • 图片 35.png

    Brand valve parts

  • 图片 36.png

    Multi-machine module combination

  • 图片 37.png

    Run smoothly

  • 图片 39.png

    Multiple anti-freeze

  • 图片 40.png

    Wide application temperature

  • 图片 41.png

    Extremely low noise

Technical Data Sheet

Product number

DPLT-60CHW-VMS

DPLT-70CHW-VMS

DPLT-85CHW-VMS

Applicable power supply

380V/50Hz

Unit type

Floor radiation type + fan coil type + radiator type

Heating

Working condition A7℃/W45℃

Rated heat capacity

60.0kW

70.0kW

85.0kW

Rated heating input power

16.76kW

19.72kW

24.22kW

Rated heating COP

3.58

3.55

3.51

  Working condition A-12℃/W41℃

Nominal heating capacity

40.0kW

46.0kW

58.0kW

Nominal heating input power

15.63kW

18.25kW

23.20kW

Nominal heating COPh

2.56

2.52

2.5

Working condition A-20°℃/W41℃

Low temperature heating capacity

34.5kW

39.0kW

50.0kW

Low temperature heating input power

15.00kW

17.49kW

22.62kW

Low temperature heating COPdh

2.3

2.23

2.21

  Working condition A-12℃/W55℃

Nominal heating capacity

38.0kW

43.5kW

54.0kW

Nominal heating input power

18.36kW

21.64kW

27.00kW

Nominal heating COPh

2.07

2.01

2

Working condition A-20°℃/W55℃

Low temperature heating capacity

32.5kW

37.2kW

45.0kW

Low temperature heating input power

17.20kW

20.00kW

24.32kW

Low temperature heating COPdh

1.89

1.86

1.85

Refrigeration

Working condition A35℃/W7℃

Rated cooling capacity

45.0kW

50.0kW

60.0kW

Rated cooling input power

15.36kW

17.48kW

20.83kW

Rated refrigeration COPc

2.93

2.86

2.88

Maximum input power

22.0kW

26.0kW

32.4kW

Maximum input current

37A

44A

55A

IPLV(H)

3.02

3

3

IPLV(C

3.85

3.82

3.8

Compressor Type

Panasonic/Panasonic DC frequency conversion + jet enthalpy increase

Fan motor type

DC inverter brushless motor

Controller Type

DC frequency conversion + 5G intelligent control

Refrigerant Type

R410A environmentally friendly

Water temperature setting range

10℃~55℃

Applicable working environment

-35℃~50℃

Connection size

DN50

DN50

DN50

Circulating water volume

 6.9m³/h

8.0m³/h

10.0m³/h

Unit noise

 59dB(A)

59dB(A)

62dB(A

Total product weight

 512kc

546kg

585kc

Net size of product

1680×750×2250mm

1680×750×2250mm

1680×750×2250mm

◆ This product complies with GB/T25127.1-2020 and GB37480-2019 standards;
◆ Due to continuous product optimization and improvement, changes in product models, parameters and designs will not be notified separately. Please refer to the product nameplate for details;